Minimax Carbon dioxide fire extinguishers provide efficient suppression for Class B and electrically actuated fires, leaving no residue. They feature safety enhancements like a rubber grip and conductive discharge hose. These extinguishers are filled in-house to ensure agent purity, offering reliable fire protection.
| Specifications | 2 kg | 3 kg | 4.5 kg |
| Fire Rating | 21B | 34B | 55B |
| Working Temperature °C | -30 °C to +60 °C | ||
| Burst Pressure | 337.5 bar min., 350 bar (actual) approx | ||
| Cylinder Testing Pressure | 250 bar for 30 sec. | ||
| Operating Pressure | 50 bar | ||
| Min. Effective Discharge Time | 8 sec. | 13 sec. | |
| Charge | Carbon Dioxide Gas | ||